Condensing units are the the most important component of whole cold room. Condensing unit typically is a high assembly of a refrigeration system which includes an assembly of compressor, condenser, fan motor, controls and a mounting plate. Ouyu Cool designs and fabricates a versatile line of air cooled, water cooled and remote condensing units ranging from small cold room monoblock refrigeration unit to very large industrial rack refrigeration system.
3.2 Low Temperature Series (Refrigerant R404A) | ||||||||
Model | UCQ02LY | UCQ03LY | UCQ04LY | UCQ05LY | UCQ06LY | UCQ08LY | ||
Room Temperature | -20ºC ~ -15 ºC | |||||||
Refrigerant | R404A | |||||||
Power supply | 380V/3Ph/50 HZ | |||||||
Compressor model | ZSI06KQE | ZSI09KQE | ZSI11KQE | ZSI15KQE | ZSI18KQE | ZSI21KQE | ||
Condenser | Fan Qty | 1 | 1 | 1 | 2 | 2 | 2 | |
Fan Voltage(V) | 220 | 220 | 220 | 220 | 220 | 220 | ||
Fan Input(W) | 60 | 60 | 60 | 60X2 | 60X2 | 60X2 | ||
Capacity. & input | Evap -20ºC |
Cap(W) | 2330 | 3240 | 4120 | 5930 | 7230 | 8060 |
Input (KW) | 1.79 | 2.25 | 2.63 | 3.59 | 4.44 | 4.9 | ||
Evap -25ºC |
Cap(W) | 1880 | 2620 | 3340 | 4830 | 5910 | 6590 | |
Input (KW) | 1.73 | 2.2 | 2.57 | 3.44 | 4.28 | 4.74 | ||
Evap -30ºC |
Cap(W) | 1500 | 2070 | 2610 | 3790 | 4780 | 5350 | |
Input (KW) | 1.66 | 2.12 | 2.44 | 3.3 | 4.17 | 4.95 | ||
pipe | Gas dia. (mm) | φ19 | φ19 | φ19 | φ19 | φ19 | φ19 | |
Liquid dia. (mm) | φ10 | φ10 | φ10 | φ10 | φ10 | φ10 | ||
Overall sizes |
L (mm) | 1020 | 1020 | 1020 | 1020 | 1020 | 1020 | |
W (mm) | 420 | 420 | 420 | 420 | 420 | 420 | ||
H (mm) | 840 | 840 | 840 | 840 | 840 | 840 | ||
Instal sizes(A×B)(mm) | 580X380 | 580X380 | 580X380 | 580X380 | 580X380 | 580X380 |
Model | UCQ02MY | UCQ03MY | UCQ04MY | UCQ05MY | UCQ06MY | UCQ07MY | UCQ08MY | UCQ09MY | UCQ10MY | UCQ13MY | UCQ15MY | ||
Room Temperature | -15ºC ~ +5 ºC | ||||||||||||
Refrigerant | R404A | ||||||||||||
Power supply | 380V/3Ph/50 HZ | ||||||||||||
Compressor model | ZB15KQE | ZB21KQE | ZB29KQE | ZB38KQE | ZB45KQE | ZB48KQE | ZB58KQE | ZB66KQE | ZB76KQE | ZB95KQE | ZB114KQE | ||
Condenser | Fan Qty | 1 | 1 | 1 | 2 | 2 | 2 | 1 | 1 | 1 | 2 | 2 | |
Fan Voltage(V) | 220 | 220 | 220 | 220 | 220 | 220 | 380 | 380 | 380 | 380 | 380 | ||
Fan Input(W) | 120 | 120 | 120 | 120×2 | 120×2 | 120×2 | 550 | 550 | 550 | 460×2 | 460×2 | ||
Capacity. & input | Evap -5ºC |
Cap(W) | 3820 | 5740 | 7840 | 9720 | 11450 | 13270 | 15250 | 17150 | 20300 | 25000 | 29700 |
Input (KW) | 1.76 | 2.5 | 3.32 | 4.2 | 4.79 | 5.24 | 6.32 | 7.09 | 8.2 | 10.5 | 12.65 | ||
Evap -10ºC |
Cap(W) | 3070 | 4680 | 6370 | 7910 | 9310 | 11047 | 12350 | 14000 | 16600 | 20000 | 24000 | |
Input (KW) | 1.82 | 2.51 | 3.35 | 4.2 | 4.81 | 5.26 | 6.31 | 7.08 | 8.2 | 10.5 | 12.65 | ||
Evap -15ºC |
Cap(W) | 2430 | 3780 | 5120 | 6380 | 7510 | 9114 | 9750 | 11300 | 13350 | 16000 | 18900 | |
Input (KW) | 1.88 | 2.52 | 3.37 | 4.2 | 4.82 | 5.27 | 6.31 | 7.06 | 8.1 | 10.5 | 12.65 | ||
Evap -20ºC |
Cap(W) | 1860 | 3010 | 4070 | 5090 | 6000 | 7442 | 7420 | 8990 | 10550 | 12200 | 14300 | |
Input (KW) | 1.93 | 2.52 | 3.39 | 4.19 | 4.81 | 5.28 | 6.31 | 7.03 | 8 | 10.6 | 12.8 | ||
pipe | Gas dia. (mm) | φ19 | φ19 | φ19 | φ19 | φ19 | φ19 | Φ28 | Φ28 | Φ28 | Φ28 | Φ28 | |
Liquid dia. (mm) | φ10 | φ10 | φ12 | φ12 | φ12 | φ12 | φ16 | φ16 | φ16 | φ16 | |||
Overall sizes | L (mm) | 1020 | 1020 | 1020 | 1020 | 1020 | 1020 | 967 | 1020 | 1020 | 1020 | 1020 | |
W (mm) | 420 | 420 | 420 | 420 | 420 | 420 | 825 | 420 | 420 | 420 | 420 | ||
H (mm) | 840 | 840 | 840 | 1240 | 1240 | 1240 | 1035 | 840 | 840 | 1240 | 1240 | ||
Instal sizes(A×B)(mm) | 580×380 | 580×380 | 580×380 | 580×380 | 580×380 | 580×380 | 570×785 | 570×785 | 570×785 | 900×785 | 900×785 | ||
Remark:1) Cooling capacity at condensing Temp. 45ºC 2) 220V/50Hz power is available for 2HP~4HP units. | |||||||||||||
3) The matched evaporators for these units should be equipped with 220V single phase fan motor. |